Security Door Controls 602RF 1A 12/24VDC Regulated Power Supply with Charger Emergency Release InputSecurity Door Controls 602RF is a powerful 1 Amp regulated and filtered power supply, designed specifically for access control systems. This robust unit operates on 12/24 VDC and features a compact metal enclosure measuring 12" x 12" x 4", making it an ideal choice for various applications, including electric locking devices and multi-door setups. One of the standout features of the 602RF is its ability to provide clean, steady power essential for preventing common access control issues. It includes an isolated battery charging circuit that maintains optimal voltage levels while preventing over-voltage scenarios, ensuring the longevity of your system components. With built-in surge protection for both input and output, the 602RF safeguards against damaging transients and voltage spikes, which are critical in high-demand environments. The power supply also comes equipped with visual status indicators that alert users to the AC input, DC output, and battery backup status. Additional functionalities include a fire/emergency release input for immediate lock release during emergencies and a low battery disconnect feature to prevent battery damage. Weighing in at 9 lbs, the 602RF is UL certified, ensuring reliable performance and compliance with safety standards. Whether for commercial or residential use, Security Door Controls 602RF is a dependable choice for your power supply needs.
1 Amp 12/24VDC Regulated and Filtered Power Supply With Charger, Emergency Release Input, Input, Output and Battery Status LED's, Boxed 11-1/4in x 11-1/4in x 3-1/5in
Notice: The info below is not item specific.
Access control system power requirements are uniquely different from other systems. Unlike camera system power requirements, access control systems draw more current for locking hardware and during access control-related events. 75 – 85% of access control operating problems and technical support calls are due to power issues. Access control systems require steady and clean (filtered) low-voltage DC current with surge suppression to protect printed circuit boards and connected devices from damage due to dirty power (transients and voltage spikes). SDC power supplies have been developed specifically to help reduce power system issues and to support electric locks and access control requirements. Our hybrid design combines the efficiency of switching power supplies with the inductive load handling capability of linear power supplies in various 12/24 VDC current output capabilities and enclosure sizes. Filtering and output voltage regulation provide protection and ensure the longevity of all system components. The high performance, heavy-duty circuitry is ideal for inductive loads and multi-door applications. With the addition of SDC programmable controllers or relay modules, the user-friendly modular designs ensure versatility, interface capability and easy installation of virtually any electric locking devices, access controls and related fire & life safety equipment.
Features:
- Regulated and filtered linear DC power
- Class 2 output
- Field selectable dual voltage
- Fire/emergency release input
- Isolated battery charging circuit
- Low battery disconnect
- Input and output surge protection
- Visual status indicator (LED)
- Cabinet enclosures with pre-configured control module mounting holes
Optional Features:
- Fire/emergency release manual reset switch
- System on/off switches
- 6’ power cord
- Key lock cover
- 230 VAC, 50/60 Hz input
- Choice of compatible door control modules
Models:
- 602RF: 1 Amp DC power controller with cabinet
- 602RFA: 1 Amp DC power controller with large cabinet
- 602RFL: 1 Amp DC power controller less cabinet
Applications:
- Fire/Emergency Release Input: A fire alarm input provides simultaneous release of all fail safe locks and door holders in case of an emergency. An optional manual reset switch following a fire/emergency release or power loss is available to meet code compliance. When the optional manual reset feature is required, should an AC power loss occur or the emergency release input be actuated, personnel must restore secondary output power manually at the power supply after the emergency release signal is reset and/or AC power is restored.
- Isolated Battery Charging Circuit: A separate charging output provides 13.5 or 27 volts to fully charge the batteries. The secondary output is always precisely maintained at 12 or 24VDC to protect locking devices and components from over voltage while the batteries are charging. The specified secondary output current is also maintained while batteries are charging. Derating of the secondary output current is not required when charging batteries.
- Low Battery Disconnect: Batteries are disconnected from the output circuit prior to deep discharge preventing battery destruction. Batteries are not included and should be ordered separately.
- Door Control Modules: Door control relay modules are available to meet virtually any application need. All wiring for lock hardware, access controls, remote controls and monitoring is terminated at one central location. Installation and troubleshooting is simplified. Modules may be factory installed or ordered separately for field installation as needed. Cabinet enclosures are preconfigured with mounting holes to accommodate door control modules. All modules are individually fused for protection of multiple station systems.
- Input and Output Surge Protection: Input and output surge protection is built-in. The AC input voltage is circuit breaker protected and the outputs are PTC protected.
- Visual Status Indicator (LED): LED tri-color status indicators provide information regarding the AC input, DC output and battery backup status.
- System On/Off Switches: Optional System On/Off switches are available both inside the cabinet enclosure or on the cabinet enclosure cover.
- 6' Power Cord: An optional 6’ power cord simplifies installations that do not require conduit where permitted by code.
- Key Lock Cover: Optional key lock cover available where tamper-resistance is required.
- International Standard Input: Additionally an alternative 230VAC international standard input is an available option.
602RF Specifications:
- Input: 115 VAC, 800 mA, 50/60 Hz
- Output: 12/24 VDC, 1 Amp
- Battery Charger: 13.5/27 VDC, 250 mA
- Cabinet: 12" x 12" x 4", 20 Guage
- Weight: 9lbs
602RFA Specifications:
- Input: 115 VAC, 800 mA, 50/60 Hz
- Output: 12/24 VDC, 1 Amp
- Battery Charger: 13.5/27 VDC, 250 mA
- Cabinet: 16" x 14" x 6-1/2", 16 gauge
- Weight: 20lbs
602RFL Specifications:
- Input: 115 VAC, 800 mA, 50/60 Hz
- Output: 12/24 VDC, 1 Amp
- Battery Charger: 13.5/27 VDC, 250 mA
- Weight: 3lbs
Attributes
Alternate Codes: 602RF
Category: Access Control, Alarm Power Supplies, Alarms & Intercom, Burglar Alarms, CCTV Products, Power Supplies, Wire & Power Supplies
Certifications: UL 294, UL 603, ULC-S318
Door Application: Power Supplies
Enclosure: Metal
Enclosure Dimensions: 12" x 12" x 4" (H x W x D)
Feedback: Audible Low Battery Alert, LED Indicator
Input Current: 800 mA @ 115VAC
Input Voltage: 115V
Input Voltage Type: VAC - Alternating
Manufacturer: Security Door Controls
Output Current: 1A @ 12/24VDC
Output Voltage: 12V, 24V
Output Voltage Type: Field Selectable, VDC - Direct
Power Supply Type: Access Control Power Supply
Series: 602
Weight: 9lbs
Resources